Availability: | |
---|---|
Quantity: | |
Input isolation transformer (customized) and output isolation transformer can achieve complete electrical isolation of UPS input and output
In the absence of mains power, DC cold start can be achieved through batteries
Intelligent fan speed control can greatly reduce noise under redundant operation
Using high-power module packaging devices, it can withstand motor-type impact loads and short-circuit current impacts
Optional reverse energy braking device (negative power absorption module) to ensure stable operation of the load
Extremely wide input voltage and frequency range, which can adapt to harsh power grid environments
Using high-performance circuit breakers to ensure the coordination of protection actions of upstream and downstream power supply systems
Can access two independent mains to adapt to dual power supply systems
Multiple machines in parallel to achieve redundancy or capacity expansion
Redundant topology structure to ensure power supply safety of loads under various conditions
Model | CT01033TL | CT01533TL | CT02033TL | CT03033TL | CT04033TL | CT06033TL | CT01033WTL |
Capacity | 10kVA/8kW | 15kVA/12kW | 20kVA/16kW | 30kVA/24kW | 40kVA/32kW | 60kVA/48kW | 100kVA/80kW |
Phase | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output |
Input Voltage Range | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load |
Frequency Range | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz |
Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
Output Voltage Range | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) |
Voltage Regulation | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) |
Frequency Range (Synchronization Range) | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz |
Overload (Utility Mode) | 105%-110%: 30 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 30 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 30 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 30 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 30 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 30 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | |
Overload (Battery Mode) | 105%-110%: 3 minutes; 110%-125%: 1 minute; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 3 minutes; 110%-125%: 1 minute; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 3 minutes; 110%-125%: 1 minute; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 3 minutes; 110%-125%: 1 minute; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 3 minutes; 110%-125%: 1 minute; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 3 minutes; 110%-125%: 1 minute; 125%-150%: 1 minute; >150%: 200ms | |
Harmonic Distortion | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) |
Transfer Time (Utility to Battery) | 0ms | 0ms | 0ms | 0ms | 0ms | 0ms | 0ms |
Transfer Time (Inverter to Bypass) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) |
Transfer Time (Inverter to ECO) | ≤10ms | ≤10ms | ≤10ms | ≤10ms | ≤10ms | ≤10ms | ≤10ms |
Efficiency (Utility Mode) | 88% | 88% | 88% | 88% | 88% | 88% | 88% |
Efficiency (Battery Mode) | 92% | 92% | 92% | 92% | 92% | 92% | |
Battery Model | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application |
Number of Batteries | 16/18 | 16/18 | 16/18 | 16/18 | 16/18 | 16/18 | 16/18 |
Dimensions (Depth x Width x Height mm) | 562 x 250 x 830 | 562 x 250 x 830 | 107 x 300 x 1000 | 107 x 300 x 1000 | 107 x 300 x 1000 | 107 x 300 x 1000 | 115 x 600 x 1200 |
Net Weight (kg) | 84 | 107 | 107 | 115 | 86 | ||
Operating Environment | Humidity: 0~95%RH@0~50°C (Non-condensing) | Altitude: <1000m | Noise: <60dB@1 meter | Humidity: 0~95%RH@0~50°C (Non-condensing) | Altitude: <1000m | Noise: <62dB@1 meter | Humidity: 0~95%RH@0~50°C (Non-condensing) |
Control Management | Support for Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, and MAC | Support for SNMP management and network browser power management |