Output isolation design to withstand various loads
Output power factor 0.8
Fully coated PCBA to withstand harsh environments
Unique ventilation design for effective heat dissipation
Wide input voltage and frequency range to withstand robust environments
High short-circuit and overload capabilities
Built-in maintenance bypass switch
Model | CT00511WTL | CT00611WTL | CT00711WTL | CT01011WTL | CT01011WTL |
Capacity | 5kVA/4kW | 6kVA/4.8kW | 7.5kVA/6kW | 10kVA/6kW | 10kVA/8kW |
Phase | Single Phase Input, Single Phase Output | Single Phase Input, Single Phase Output | Single Phase Input, Single Phase Output | Single Phase Input, Single Phase Output | Single Phase Input, Single Phase Output |
Input Voltage Range | 165~285VAC@16 battery; 185~285VAC@18 battery | 165~285VAC@16 battery; 185~285VAC@18 battery | 165~285VAC@16 battery; 185~285VAC@18 battery | 165~285VAC@16 battery; 185~285VAC@18 battery | 165~285VAC@16 battery; 185~285VAC@18 battery |
Frequency Range | 40~55Hz or 56~64Hz | 40~55Hz or 56~64Hz | 40~55Hz or 56~64Hz | 40~55Hz or 56~64Hz | 40~55Hz or 56~64Hz |
Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
Output Voltage Range | 208*/220/230VAC | 208*/220/230VAC | 208*/220/230VAC | 208*/220/230VAC | 208*/220/230VAC |
Voltage Regulation | ±1% | ±1% | ±1% | ±1% | ±1% |
Frequency Range (Synchronization Range) | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz |
Overload (Utility Mode) | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second |
Overload (Battery Mode) | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second |
Harmonic Distortion | ≤3% (Linear Load); ≤5% (Non-linear Load) | ≤3% (Linear Load); ≤5% (Non-linear Load) | ≤3% (Linear Load); ≤5% (Non-linear Load) | ≤3% (Linear Load); ≤5% (Non-linear Load) | ≤3% (Linear Load); ≤5% (Non-linear Load) |
Transfer Time (Utility to Battery) | 0ms | 0ms | 0ms | 0ms | 0ms |
Transfer Time (Inverter to Bypass) | 0ms | 0ms | 0ms | 0ms | 0ms |
Transfer Time (Inverter to ECO) | ≤10ms | ≤10ms | ≤10ms | ≤10ms | ≤10ms |
Efficiency (Utility Mode) | 88% | 88% | 88% | 88% | 88% |
Efficiency (Battery Mode) | 92% | 92% | 92% | 92% | |
Battery Model | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application |
Number of Batteries | 16/18 | 16/18 | 16/18 | 16/18 | 16/18 |
Dimensions (Depth x Width x Height mm) | 562 x 250 x 830 | 562 x 250 x 830 | 562 x 250 x 830 | 562 x 250 x 830 | |
Net Weight (kg) | 62 | 78 | 78 | 86 | 86 |
Operating Environment | Humidity: 0~95%RH@0~50°C (Non-condensing) | Altitude: <1000m | Noise: <58dB@1 meter | Humidity: 0~95%RH@0~50°C (Non-condensing) | Altitude: <1000m |