Pure double conversion technology
DSP technology ensures high performance output power factor 1.0
All-phase active power factor correction 50Hz/60Hz inverter mode Energy-saving ECO mode operation
Emergency shutdown function (EPO) Generator compatible
Dual AC input
Optional parallel operation, can share batteries
Three-stage charging design to optimize battery performance Adjustable number of batteries
Standard maintenance bypass
Power supply walk-in function
Optional isolation transformer
Model | CT01033TL | CT01533TL | CT02033TL | CT03033TL | CT04033TL | CT06033TL |
Capacity | 10kVA/10kW | 15kVA/15kW | 20kVA/20kW | 30kVA/30kW | 40kVA/40kW | 60kVA/60kW |
Phase | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output |
Input Voltage Range | 110-300VAC@50% load; 176-276VAC@100% load | 110-300VAC@50% load; 176-276VAC@100% load | 110-300VAC@50% load; 176-276VAC@100% load | 110-300VAC@50% load; 176-276VAC@100% load | 110-300VAC@50% load; 176-276VAC@100% load | 110-300VAC@50% load; 176-276VAC@100% load |
Frequency Range | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz |
Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
Output Voltage Range | 3 x 360*/380/400/415VAC (3Ph+N) | 3 x 360*/380/400/415VAC (3Ph+N) | 3 x 360*/380/400/415VAC (3Ph+N) | 3 x 360*/380/400/415VAC (3Ph+N) | 3 x 360*/380/400/415VAC (3Ph+N) | 3 x 360*/380/400/415VAC (3Ph+N) |
Voltage Regulation | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% |
Frequency Range (Synchronization Range) | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz |
Overload (Utility Mode) | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate |
Overload (Battery Mode) | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | 100%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: Immediate | |
Harmonic Distortion | ≤2% (Linear Load); ≤5% (Non-linear Load) | ≤2% (Linear Load); ≤5% (Non-linear Load) | ≤2% (Linear Load); ≤5% (Non-linear Load) | ≤2% (Linear Load); ≤5% (Non-linear Load) | ≤2% (Linear Load); ≤5% (Non-linear Load) | ≤2% (Linear Load); ≤5% (Non-linear Load) |
Transfer Time (Utility to Battery) | 0ms | 0ms | 0ms | 0ms | 0ms | 0ms |
Transfer Time (Inverter to Bypass) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) |
Transfer Time (Inverter to ECO) | 0ms (Utility Loss, <10ms) | 0ms (Utility Loss, <10ms) | 0ms (Utility Loss, <10ms) | 0ms (Utility Loss, <10ms) | 0ms (Utility Loss, <10ms) | 0ms (Utility Loss, <10ms) |
Efficiency (Utility Mode) | 95.50% | 95.50% | 95.50% | 95.50% | 95.50% | 95.50% |
Efficiency (Battery Mode) | 94.50% | 94.50% | 94.50% | 94.50% | 94.50% | 94.50% |
Battery Model | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application |
Number of Batteries | 20 | 32-40 | 32-40 | 32-40 | 32-40 | 32-40 |
Dimensions (Depth x Width x Height mm) | 630 x 250 x 826 | 630 x 250 x 826 | 630 x 250 x 826 | 630 x 250 x 826 | 780 x 300 x 1000 | 780 x 300 x 1000 |
Net Weight (kg) | 28 | 43 | 43 | 55 | 58 | 87 |
Operating Environment | Humidity: 0~95%RH@0~40°C (Non-condensing) | Altitude: <1000m | Noise: <60dB@1 meter | Humidity: 0~95%RH@0~40°C (Non-condensing) | Altitude: <1000m | Noise: <62dB@1 meter |