Availability: | |
---|---|
Quantity: | |
Modular design, easy to expand
Output power factor OutputPF=1 (kVA=kW)
N+1orN+R parallel redundant application design increases system flexibility, stability and safety
Modular design is applied to power modules, STS modules and battery modules
Easy to update and maintain, which can reduce after-sales maintenance costs
Charging current is adjustable, and the maximum charging current of each module can reach 8A/6A
5.7-inch LCD graphical design, the display is more intuitive and clear
Optional 10-inch touch LCD screen
Model | CT90 | CT120 | CT180 |
Capacity | 90kVA/90kW | 120kVA/120kW | 180kVA/180kW |
Power Module Capacity | 30kVA/30kW | 30kVA/30kW | 30kVA/30kW |
Number of Power Modules Installed | 3 | 4 | 6 |
Phase | Three-phase input, three-phase output | Three-phase input, three-phase output | Three-phase input, three-phase output |
Input Voltage Range | 208~304VAC@70% load; 305~478VAC@100% load | 208~304VAC@70% load; 305~478VAC@100% load | 208~304VAC@70% load; 305~478VAC@100% load |
Frequency Range | 40~70Hz | 40~70Hz | 40~70Hz |
Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
Output Voltage Range | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) |
Voltage Regulation | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) |
Frequency Range (Synchronization Range) | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz |
Overload (Utility Mode) | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms |
Overload (Battery Mode) | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms |
Harmonic Distortion | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) |
Transfer Time (Inverter to Bypass) | ≤20ms | ≤20ms | ≤20ms |
Efficiency | 94.50% | 94.50% | 94.50% |
Battery Model | Varies by Application | Varies by Application | Varies by Application |
Number of Batteries | 32-40 | 32-40 | 32-40 |
Dimensions (Depth x Width x Height mm) | 1000 x 515 x 763 | 1100 x 600 x 1475 | 1100 x 600 x 1475 |
Net Weight (kg) | 77 | 335 | 437.5 |
Operating Environment | Humidity: 0~95%RH@0~40°C (Non-condensing) | Altitude: <1000m | Noise: <68.2dB@1 meter |
Control Management | Support for Windows 2000/2003/XP/Vista/2008/7/8, Linux, and MAC | Support for SNMP management and network browser power management |