Availability: | |
---|---|
Quantity: | |
Pluggable power module design, front-end access is reduced
MTTR, parallel redundancy capability ensures power
Built-in power walk-in function, can be used for parallel operation
With shared battery characteristics
Dual power input
Built-in 4 switches, including AC input, bypass input/output and maintenance bypass switch
Adjustable number of batteries and charging current
Output power factor 1.0
Full-phase active power factor correction
Built-in 7-inch touch LCD screen, providing comprehensive information
Emergency Power Off (EPO)
Compatible with generator input
50Hz/60Hz variable frequency conversion mode
Model | CT08033TL | CT10033TL | CT12033TL | CT18033TL | CT20033TL |
Capacity | 80kVA/80kW | 100kVA/100kW | 120kVA/120kW | 180kVA/180kW | 200kVA/200kW |
Phase | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output | Three Phase Input, Three Phase Output |
Input Voltage Range | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load | 208-304VAC@70% load; 305~478VAC@100% load |
Frequency Range | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz |
Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
Output Voltage Range | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) | 3 x 380/400/415VAC (3Ph+N) |
Voltage Regulation | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) | ±1% (balanced load); ±2% (unbalanced load) |
Frequency Range (Synchronization Range) | 46-54Hz or 56-64Hz | 46-54Hz or 56-64Hz | 46-54Hz or 56-64Hz | 46-54Hz or 56-64Hz | 46-54Hz or 56-64Hz |
Overload (Utility Mode) | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms |
Overload (Battery Mode) | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 200ms |
Harmonic Distortion | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) | <2% (Linear Load); <4% (Non-linear Load) |
Transfer Time (Utility to Battery) | 0ms | 0ms | 0ms | 0ms | 0ms |
Transfer Time (Inverter to Bypass) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) | 0ms (Phase Failure, <4ms Interruption) |
Transfer Time (Inverter to ECO) | ≤10ms | ≤10ms | ≤10ms | ≤10ms | ≤10ms |
Efficiency (Utility Mode) | 95.50% | 95.50% | 95.50% | 95.50% | 95.50% |
Efficiency (Battery Mode) | 94.50% | 94.50% | 94.50% | 94.50% | 94.50% |
Battery Model | Varies by Application | Varies by Application | Varies by Application | Varies by Application | Varies by Application |
Number of Batteries | 32-40 | 32-40 | 32-40 | 32-40 | 32-40 |
Dimensions (Depth x Width x Height mm) | 1000 x 430 x 1200 | 1000 x 430 x 1200 | 1000 x 430 x 1200 | 1000 x 600 x 1200 | 1000 x 600 x 1200 |
Net Weight (kg) | 200 | 168 | 168 | 265 | 265 |
Operating Environment | Humidity: 0~95%RH@0~40°C (Non-condensing) | Altitude: <1000m | Noise: <75dB@1 meter | Humidity: 0~95%RH@0~40°C (Non-condensing) | Altitude: <1000m |
Control Management | Support for Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, and MAC | Support for SNMP management and network browser power management |